Email Id: info@ufs.co.in , contact@ufs.co.in , salesfed@ufs.co.in

Call Us: 

call

 +91 09818683042

ABC Stored Pressure Type Fire Extinguisher

APPLICATIONS
  • UFS dry powder type extinguishers are designed for protection of light and ordinary hazards.
  • Suitable for A,B,C & E fire classes such as wood, paper, plastic, rubber, flammable liquids, gases and electric fire.
  • Reliable components are carefully chosen to give maximum efficiency along with high quality agent to achieve high performance.
FEATURES
  • Deep drawn container made of high tensile cold rolled sheet.
  • Minimum welding points to give attractive appearance.
  • UFS Extinguishers pressurized to 15 bar and 100 % leakage tested.
  • The epoxy powder coating of 50 to 90 micron thickness provides inner & outer surface of the body.
  • The easy squeeze grip type control valve provides for quick activation of the Extinguisher.
  • Easy operation, maintenance, refilling and service.
  • UFS extinguishers designed in compliance with BIS Standards.
abc
TECHNICAL SPECIFICATIONS
  Capacity(Kg)

1 Kg

2 Kg

4 Kg

6 Kg

9 Kg

  Body material

Mild steel sheet

Mild Steel sheet

Mild steel sheet

Mild steel sheet

Mild steel sheet

  Body sheet thickness (mm)

1.5 mm

1.5 mm

1.5 mm

1.5 mm

1.7 to 1.8 mm

  Extinguishing agent

Dry powder Map(ABC) IS: 14609

Dry powder Map(ABC)
IS: 14609

Dry powder Map(ABC) IS: 14609

Dry powder Map(ABC) IS: 14609

Dry powder Map(ABC) IS: 14609

  Propelling gas (Nitrogen)

15 bar

15 bar

15 bar

15 bar

15 bar

  Discharge time (sec.)

Minimum 8 sec.

Minimum 8 sec.

Minimum 13 sec.

Minimum13 sec.

Minimum13sec.

  Service pressure

15 - 19 bar

15 - 19 bar

15 - 19 bar

15 - 19 bar

15 - 19 bar

  Hydraulic test pressure

35 bar

35 bar

35 bar

35 bar

35 bar

  Operating temperature

-10°C to +55 °C

-10 °C to +55 °C

-10 °C to +55 °C

-10 °C to +55 °C

-10 °C to +55 °C

  Body burst pressure

Minimum 55 bar

Minimum 55 bar

Minimum 55 bar

Minimum 55 bar

Minimum 55 bar

  Hose / Nozzle

Nozzle

Nozzle

Hose Minimum 400 mm

Hose Minimum 400 mm

Hose Minimum 400 mm

  Dimension( OD ) mm

87 mm

110 mm

150 mm

150 mm

175 mm

  Discharge throw (meter)

1 - 2 mtr

1 - 2 mtr

2 - 3 mtr

2 - 5 mtr

2 - 6 mtr

  Fire Rating

1A & 8B

1A & 8B

2A & 21B

3A & 21B

3A & 34B